Conditions of Use: |
Alternator |
---|---|
Usage: | Common Units |
Output Type: | AC Single Phase |
Still deciding? Get samples of US$ 130/pcs
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
DC SUPPLY
|
CONTINUOUS VOLTAGE RATING
|
8 V to 35 V Continuous
|
MAXIMUM OPERATING CURRENT
|
50mA
|
|
MAINS (UTILITY)
|
VOLTAGE RANGE
|
75V(L-N) to 333V AC (L-N) absolute maximum
|
FREQUENCY RANGE
|
50Hz-60Hz at rated engine speed
|
|
OUTPUTS
|
OUTPUT A (FUEL)
|
1.2 Amp DC at supply voltage. Switches to battery negative when active |
OUTPUT B (START)
|
1.2 Amp DC at supply voltage. Switches to battery negative when active |
|
OUTPUTS C & D
|
2 A DC at supply voltage
|
|
AUXILIARY OUTPUTS E,F,G,H
|
2 A DC at supply voltage
|
|
GENERATOR
|
VOLTAGE RANGE
|
15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph) |
FREQUENCY RANGE
|
3.5 Hz to 75 Hz
|
|
MAGNETIC PICK-UP
|
VOLTAGE RANGE
|
+/- 0.5 V to 70 V
|
FREQUENCY RANGE
|
10,000 Hz (max)
|